An OT asset register records, per device, what it is, where it is, which zone and Purdue level it belongs to, what runs on it, how it is reached, who is responsible, whether it is still supported, how critical it is, and where its backup is. A passive sensor shows what talks on the network today; a register also holds what no capture can see. The work is keeping the two in agreement.
What public guidance asks for
Three public sources frame the question.
The joint guidance Foundations for OT Cybersecurity: Asset Inventory Guidance for Owners and Operators (CISA with EPA, NSA, FBI and the cyber agencies of Australia, Canada, Germany, the Netherlands and New Zealand, 13 August 2025) describes five steps: define scope and objectives, identify assets and collect attributes, create a taxonomy, manage the data, and manage the life cycle. Its Appendix A ranks attributes as high, medium or low priority. For the taxonomy it uses the zones and conduits of the ISA/IEC 62443 series.
NIST SP 800-82 Rev. 3, Guide to Operational Technology (OT) Security (September 2023), asks for unique identifiers, a hardware inventory with device details and location, a software and firmware inventory with version numbers, vendor information, and documented roles and responsibilities. It ties a complete and accurate inventory to risk assessment, vulnerability management and obsolescence tracking.
The ISA/IEC 62443 series is the standard set for industrial automation and control systems. Part 3-2 covers dividing a system into zones and conduits and setting a target security level for each.
The fields, why they matter and where they come from
| Field | Why it matters | Where the data comes from |
|---|---|---|
| Identity: asset number, name, role or type, manufacturer, model, serial number | Without a unique identifier nothing else can be attached to the device. Manufacturer and model are what vulnerability advisories are matched on. | Nameplate, purchase records, the integrator’s hardware list |
| Location: site, building, line, cabinet | Someone has to find the device, often during a fault. | Walk-down, electrical drawings |
| Zone | Places the device with others that need the same protection, and decides which conduits its traffic may use. | A design decision, recorded after the risk assessment |
| Purdue level | Says how close the device is to the process and is a quick filter for “what can reach the controllers”. | Role of the device, network architecture |
| Firmware and software versions, operating system | Known vulnerabilities and available updates depend on the exact version. | Engineering tool, device web page or display, commissioning records |
| Network addresses: IP, MAC, hostname, VLAN | Needed to relate captures, firewall rules and logs to a device. | IP plan, switch and controller configuration, captures |
| Protocols, ports and services | Show the attack surface and what a firewall between zones has to allow. The CISA guidance warns that ports and services are time consuming to maintain and suggests starting with assets that communicate across the OT perimeter. | Design documents, captures |
| Owner | Someone must be able to decide about a change, an outage or a risk. | Organisation chart, maintenance contracts |
| Supplier and support status | Tells who to call and whether security fixes still appear. An unsupported device needs other protection. | Supplier contract, the manufacturer’s lifecycle notices |
| Criticality | Sets the order of work: what is protected, patched and restored first. | Risk assessment with production and safety staff |
| Backup location and last restore test | A backup that was never restored is an assumption. NIST asks for a list of maintained backups and for the restoration process to be tested. | Backup system, the engineering station, a dated test record |
In the CISA ranking, criticality, role, manufacturer, model, addresses, protocols and location are high priority; firmware and software version, owner, and backup frequency and type are medium. That ranking is a starting order, not a reason to leave the medium fields empty.
Documented state and observed state
There are two ways to know a plant network.
The documented state is the register and the drawings: what was designed, installed and decided. It contains intent. It also contains things no network shows: the owner, the criticality, the backup, a device that is switched off, a spare on a shelf, a drive on a serial bus behind a gateway.
The observed state comes from a passive sensor or a packet capture: which addresses exist, what they talk and to whom. According to NIST SP 800-82 Rev. 3, passive scanning adds no traffic to the network and can identify the devices that actively communicate on the monitored segments, sometimes down to manufacturer, part number and firmware version. The same section states its limits: it cannot identify devices that are not communicating, it cannot inspect encrypted traffic without special provisioning, and it often takes days. Active scanning sees more, and NIST advises extreme caution with it on an operational network.
Neither state is the truth alone. The CISA guidance asks for both physical inspection and a logical survey, and for the scope to include assets found in documentation as well as on the floor. The differences are the findings:
- A host in the capture that the register does not know: an undocumented device, or a supplier’s remote-access router.
- A device in the register that never appears in a capture: switched off, removed, or on a segment the sensor does not see.
- A flow between two zones that no conduit covers: a path nobody decided on.
- A firmware version on the wire that differs from the one written down.
Comparing the two, deciding which side is wrong, and correcting it is the recurring work. A register that is never checked against a capture drifts; a sensor without a register produces a list nobody owns.
How netbox-ot holds these fields
NetBox is an open-source inventory for networks and devices. Packetflow’s open-source plugin netbox-ot (0.4.1 at the time of writing) adds the OT part. According to its documentation the fields land as follows.
| Field | Where it lives |
|---|---|
| Identity, location, serial number, network addresses | Core NetBox: devices, modules (a PLC’s CPU and I/O cards), sites, locations, racks, IP addresses |
| Zone | netbox-ot Zone, with member devices, virtual machines and prefixes |
| Purdue level | Custom field ot_purdue_level on devices and virtual machines |
| Firmware version | Custom field ot_firmware_version on devices and modules, since 0.3.0 |
| Protocols and services | netbox-ot Industrial service, linked to a NetBox application service for ports, and Fieldbus for serial segments |
| Accountable person | A NetBox contact on each zone and conduit |
| Support status | End of support per device, when the optional netbox-lifecycle plugin is installed |
The documentation describes no dedicated field for criticality per device or for backup location and restore test. Zones carry security levels and risk assessments; the other two are candidates for NetBox custom fields.
For the comparison, the ot_import command reads Zeek logs or a documented JSON format. It reports the observed hosts that match no device in NetBox, never creates devices itself, and records when each flow was first and last seen. A flow not seen for 90 days (the default of stale_after_days) is listed under Needs attention. The plugin captures no traffic: it reads what a sensor already wrote. It is a register in alpha, not a monitoring product and not a certificate.
Sources
- Foundations for OT Cybersecurity: Asset Inventory Guidance for Owners and Operators (CISA and partners, August 2025) and the PDF
- NIST SP 800-82 Rev. 3, Guide to Operational Technology (OT) Security
- ISA/IEC 62443 series of standards (ISA)
- IEC 62443-3-2:2020 (IEC webstore abstract)
- netbox-ot on GitHub: data model, importer, companion plugins
- netbox-ot on PyPI
- ot-devicetypes on GitHub