OT asset register: what to record per device

The fields an OT asset inventory needs per device, why each matters, where the data comes from, and how a register differs from what a sensor shows.

An OT asset register records, per device, what it is, where it is, which zone and Purdue level it belongs to, what runs on it, how it is reached, who is responsible, whether it is still supported, how critical it is, and where its backup is. A passive sensor shows what talks on the network today; a register also holds what no capture can see. The work is keeping the two in agreement.

What public guidance asks for

Three public sources frame the question.

The joint guidance Foundations for OT Cybersecurity: Asset Inventory Guidance for Owners and Operators (CISA with EPA, NSA, FBI and the cyber agencies of Australia, Canada, Germany, the Netherlands and New Zealand, 13 August 2025) describes five steps: define scope and objectives, identify assets and collect attributes, create a taxonomy, manage the data, and manage the life cycle. Its Appendix A ranks attributes as high, medium or low priority. For the taxonomy it uses the zones and conduits of the ISA/IEC 62443 series.

NIST SP 800-82 Rev. 3, Guide to Operational Technology (OT) Security (September 2023), asks for unique identifiers, a hardware inventory with device details and location, a software and firmware inventory with version numbers, vendor information, and documented roles and responsibilities. It ties a complete and accurate inventory to risk assessment, vulnerability management and obsolescence tracking.

The ISA/IEC 62443 series is the standard set for industrial automation and control systems. Part 3-2 covers dividing a system into zones and conduits and setting a target security level for each.

The fields, why they matter and where they come from

Field Why it matters Where the data comes from
Identity: asset number, name, role or type, manufacturer, model, serial number Without a unique identifier nothing else can be attached to the device. Manufacturer and model are what vulnerability advisories are matched on. Nameplate, purchase records, the integrator’s hardware list
Location: site, building, line, cabinet Someone has to find the device, often during a fault. Walk-down, electrical drawings
Zone Places the device with others that need the same protection, and decides which conduits its traffic may use. A design decision, recorded after the risk assessment
Purdue level Says how close the device is to the process and is a quick filter for “what can reach the controllers”. Role of the device, network architecture
Firmware and software versions, operating system Known vulnerabilities and available updates depend on the exact version. Engineering tool, device web page or display, commissioning records
Network addresses: IP, MAC, hostname, VLAN Needed to relate captures, firewall rules and logs to a device. IP plan, switch and controller configuration, captures
Protocols, ports and services Show the attack surface and what a firewall between zones has to allow. The CISA guidance warns that ports and services are time consuming to maintain and suggests starting with assets that communicate across the OT perimeter. Design documents, captures
Owner Someone must be able to decide about a change, an outage or a risk. Organisation chart, maintenance contracts
Supplier and support status Tells who to call and whether security fixes still appear. An unsupported device needs other protection. Supplier contract, the manufacturer’s lifecycle notices
Criticality Sets the order of work: what is protected, patched and restored first. Risk assessment with production and safety staff
Backup location and last restore test A backup that was never restored is an assumption. NIST asks for a list of maintained backups and for the restoration process to be tested. Backup system, the engineering station, a dated test record

In the CISA ranking, criticality, role, manufacturer, model, addresses, protocols and location are high priority; firmware and software version, owner, and backup frequency and type are medium. That ranking is a starting order, not a reason to leave the medium fields empty.

Documented state and observed state

There are two ways to know a plant network.

The documented state is the register and the drawings: what was designed, installed and decided. It contains intent. It also contains things no network shows: the owner, the criticality, the backup, a device that is switched off, a spare on a shelf, a drive on a serial bus behind a gateway.

The observed state comes from a passive sensor or a packet capture: which addresses exist, what they talk and to whom. According to NIST SP 800-82 Rev. 3, passive scanning adds no traffic to the network and can identify the devices that actively communicate on the monitored segments, sometimes down to manufacturer, part number and firmware version. The same section states its limits: it cannot identify devices that are not communicating, it cannot inspect encrypted traffic without special provisioning, and it often takes days. Active scanning sees more, and NIST advises extreme caution with it on an operational network.

Neither state is the truth alone. The CISA guidance asks for both physical inspection and a logical survey, and for the scope to include assets found in documentation as well as on the floor. The differences are the findings:

  • A host in the capture that the register does not know: an undocumented device, or a supplier’s remote-access router.
  • A device in the register that never appears in a capture: switched off, removed, or on a segment the sensor does not see.
  • A flow between two zones that no conduit covers: a path nobody decided on.
  • A firmware version on the wire that differs from the one written down.

Comparing the two, deciding which side is wrong, and correcting it is the recurring work. A register that is never checked against a capture drifts; a sensor without a register produces a list nobody owns.

How netbox-ot holds these fields

NetBox is an open-source inventory for networks and devices. Packetflow’s open-source plugin netbox-ot (0.4.1 at the time of writing) adds the OT part. According to its documentation the fields land as follows.

Field Where it lives
Identity, location, serial number, network addresses Core NetBox: devices, modules (a PLC’s CPU and I/O cards), sites, locations, racks, IP addresses
Zone netbox-ot Zone, with member devices, virtual machines and prefixes
Purdue level Custom field ot_purdue_level on devices and virtual machines
Firmware version Custom field ot_firmware_version on devices and modules, since 0.3.0
Protocols and services netbox-ot Industrial service, linked to a NetBox application service for ports, and Fieldbus for serial segments
Accountable person A NetBox contact on each zone and conduit
Support status End of support per device, when the optional netbox-lifecycle plugin is installed

The documentation describes no dedicated field for criticality per device or for backup location and restore test. Zones carry security levels and risk assessments; the other two are candidates for NetBox custom fields.

For the comparison, the ot_import command reads Zeek logs or a documented JSON format. It reports the observed hosts that match no device in NetBox, never creates devices itself, and records when each flow was first and last seen. A flow not seen for 90 days (the default of stale_after_days) is listed under Needs attention. The plugin captures no traffic: it reads what a sensor already wrote. It is a register in alpha, not a monitoring product and not a certificate.

Sources

Packetflow builds secure OT platforms for industrial plants and maintains these tools. For help setting up a register, send the NetBox version if there is one, what needs to be recorded and a sketch of the plant network through the contact page. The open tools are listed under open tooling.

Back to all articles

Frequently asked questions

  • What fields should an OT asset inventory contain?

    The 2025 CISA guidance names fourteen high-priority attributes, among them asset number, role, manufacturer, model, operating system, hostname, IP and MAC address, protocols, ports and services, physical location and criticality. Firmware version, owner and backup details follow as medium priority. A register for a plant adds the zone, the Purdue level, the support status and the date of the last restore test.

  • What is the difference between an asset register and a passive sensor?

    A register holds the documented state: what was decided, bought and installed, including things no network shows, such as owner, criticality and backups. A passive sensor holds the observed state: which addresses talk, to whom and in which protocol. Neither is complete alone, and the differences between them are the findings.

  • Can passive monitoring find every OT device?

    No. NIST SP 800-82 Rev. 3 notes that passive scanning cannot identify devices that are not actively communicating and cannot inspect encrypted traffic without special provisioning. Devices on serial fieldbuses behind a gateway, and spares on a shelf, do not appear on a monitored switch port either.

  • Is active scanning safe on an OT network?

    NIST SP 800-82 Rev. 3 advises extreme caution: active scans add traffic and may cause device instability or interfere with the process. It recommends scheduling them during planned outages where possible. Physical inspection and existing documentation carry no such risk.

  • How often should an OT asset register be updated?

    With every change. The CISA guidance asks that the inventory is updated whenever a device is introduced or removed, also under emergency change authority, and that the taxonomy is reviewed periodically. A register that is only refreshed for an audit drifts between audits.

Tell us about your project

Packetflow comes back with a design and a price, within one working day.